Skip to content
English
  • There are no suggestions because the search field is empty.

ALN-EN Specification

Intelligent (Analogue Addressable) Optical Smoke Sensor

Features

  • Removable, High Performance chamber

  • Twin LEDs allow 360° viewing – green when polling, amber when isolating, red in fire

  • Locking mechanism (sensor to base)

  • Variable sensitivity

  • Electronically addressed

  • Pulsing/non-pulsing controlled from panel*1.

  • Approved by LPCB & VdS

  • SIL Level 2 approved variant available

Description

Model ALN-EN is a Photoelectric Smoke Sensor, which is fully compatible with Hochiki’s ESP Analogue Addressable Protocol.
The ALN-EN incorporates Hochiki’s newest High Performance Chamber Technology removing the need to use Ionisation Smoke Sensors in the majority of applications. This also allows the sensor threshold level to be increased, thereby improving the signal to noise ratio and reducing
susceptibility to false alarms.
The ALN-EN smoke chamber is easily removed or replaced for cleaning and utilises a unique improved baffle design which allows smoke to enter the chamber whilst keeping out ambient light.

Specification

Ordering Code ALN-EN - Ivory / ALN-EN(WHT) - White / ALN-EN(BLK) - Black
Operating Voltage 17 – 41 VDC
Low Power Mode (typ) 120 μA (typ.)
Quiescent Current (typ) 400 μA (typ.)
Alarm Current (controlled by CIE) 9.1 mA (excluding remote indicator)
Transmission Method Digital Communications using ESP
Operating Temperature Range -10 °C to + 50 °C
Operating Humidity 95%RH - Non Condensing (at 40 °C)
Sensitivity Levels 2%/m to 4.5%/m
Storage Temperature Range -30 °C to +60 °C
Storage Humidity <80% RH at 60 °C
Colour / Case Material Ivory, White or Black / ABS
Weight (g) 95
Diameter (mm) / Height (mm) 100 / 45
Compatible Bases YBN-R/3, YBO-BS, YBO-BSB2, YBN-R/3(SCI)
Base Fixing Centres (mm) 48 ~ 74
Approvals LPCB, VdS
Wind Exposure (Ref EN54-7) 1 ± 0,2 m s-1
Ingress Protection Rating IP42

Version

Issue 6, Jul 25

Documents

ALN-EN Specification